60. Refrigeration plants
(1) Every refrigeration plant capable of being entered by an employee
shall—
(a) have all control valves situated outside the cold storage room;
and
(b) have all doors of the cold storage room capable of being opened
easily and quickly from the inside and outside.
(2) Every refrigeration plant which has a positive displacement compressor shall be provided with—
(a) an automatic pressure relief device for that compressor; and
(b) a suitable pressure gauge to indicate the discharge pressure from
such plant.
(3) Every owner of a refrigeration plant referred to in subsection (1) shall
cause a registered machinery inspector to examine, test and certify at least
once every 12 months the entire plant together with all its components and
auxiliary parts.
O2 – 43 [Issue 1]
Occupational Safety and Health Act
(4) The owner shall send the original report of the result of every such examination to the Director, Occupational Safety and Health in the form set out in
the Twentieth Schedule within 28 days of the completion of the examination.